++++General:
KYN61-40.5( same as unigear Z3.2) air-insulated metal-clad withdrawable switchgear( hereinafter as "switchgear") is a kind of MV switchgear.
It is designed as withdrawable module type panel, and the withdrawable part is fitted with VD4-36E, VD4-40.5 withdrawable vacuum circuit breaker manufactured by Cooper Nature company. It can also be fitted with isolation truck, PT truck, fuses truck and so on. It is applicable to three phase AC 50/60 Hz power system, and mainly used for the transmission and distribution of electrical power and control, protection, monitoring of the circuit.
++++Standards and specifications:
IEC60694 The commo n technical requirements of high voltage switchgear and controlgear IEC62271-200 A.C. metal enclosed switchgear and controlgear at the rated voltage of 1kV~52k V IEC62271-100 High voltage switchgear and controlgear-Part 100:Hi gh voltage A.C. circuit breaker GB3906 3.6~ 40.5kV alternating current metal enclosed switchgea r and controlgear GB1984 High voltage alternating current circuit breaker GB/T11022 The commo n technical requirements of high voltage switchgear and controlgear DL/T404 3.6~ 40.5kV alternating current metal enclosed switchgea r and controlgear++++Service conditions:
a. Ambient temperature: Maximum temperature:+40℃ Minimum temperature: -15℃
b. Ambient humidity: Daily average RH no more than 95%;Monthly average RH no more than 90%
c. Altitude no higher than 2500m;
d. The air around without any pollution of duty,smoke,ercode or flammable air,steam or salty fog;
++++Main technical specifications:
No. | Item | Unit | Parameters |
1 | Rated Voltage | KV | 36 | 40.5 |
2 | Rated Frequency | Hz | 50/60 |
3 | Rated Current | A | 630 1250 1600 2000 2500 3150 |
4 | Branch busbar rated current | A | 630 1250 1600 2000 2500 3150 |
5 | Main busbar rated current | A | 630 1250 1600 2000 2500 3150 |
6 | 1min power frequency withstand voltage | KV | 70 | 95 |
7 | Lightening impulse withstand voltage | kV | 170 | 185 |
8 | Rated Short-time Withstand Current (4s) | kA | 20/25/31.5/40 |
9 | Rated Short Circuit Breaking Current(Peak) | kA | 40/50/63/80/100 |
10 | Protection type |
| IP4X for housing |
11 | Rated voltage for control Circuit | V | DC110, DC220, AC220 |